4.A2CCPU
-------------------
MELSEC·A
4.8
Precautions
on
Handling
(1) Resin terminal connectors and pin connectors are used by the A2C CPU I
unit. Do not drop the CPU unit or apply hard shock to the unit.
(2) Never remove PCBs from the module.
If a PCB is removed, it will cause
trouble.
(3) Observe tightening torque for each screw.
SCrew.
Torque
kg-em
(Ib-In)
Terminal screws (terminal block)
8.5 (7.36) to 11.5 (9.96)
(M3.S screws)
Module mounting screws (M4 screws) 8 (6.93) to 12 (10.4)
(4) M4 screws should be 10 to 14 mm (0.39 to 0.55 in) long.