8. MAINTENANCE AND INSPECTION
___________________
MELSEC·A
8.3.2 Replacing procedures
I
(1) Procedures
(a) Turn off
the
A2C.
(b) Disconnect
the
battery lead
connector
from
the
connector
on
the
A2C board.
(c) Remove
the
battery from
the
battery
holder
by pressing
down
the
holder
lug.
(d) Insert a new battery.
(e) Connect
the
battery lead
connector
with
the
battery
connector
on
the
A2C board.
(I) Turn on
the
A2C.
(g) Check that
the
low battery flag (M9006) is reset. If it is set, replace
the
battery again.
(2) Caution
Replace the battery within
the
guaranteed
period specified in Table 8.4.
If it takes
longer
than
the
guaranteed period, sequence
programs
or
latched data would be lost.
Table
8.4
Capacitor
Backup
Time
Capacitor backUp time (mInute)
Guaranteed period (MINIMUM)
Under normal operating conditions (TYP)
•
9
20
A2CCPU
A2CCPUP21/R21
Red lead
Battery lead connector
Battery
~E~~~~
Blue lead
Board connector
8-4