4.2.10 Output from the ERRterminals
The ERR terminals are used to output
the
signals of MINI-53 link line errors
and self-diagnosis errors (at operation stop) mentioned below. Output of
these signals is enabled even when the A2C has
stopped
operation with the
sequence program. (When
the
ERR terminals are turned ON. M9090 is also
turned ON.)
Output of error signals other than those mentioned below is also enabled
from ERR terminals by turning ON M9089 by use of
the
sequence program.
Error.
ERR
Error
RUN
MIOIO
terminals
LED
LED
Initial setting circuit error OFF
OFF
• Communication error due to
line
breakage
MINI-S3
link line
• Station error in the stop at
Lit Lit
errors
faulty station detection mode
ON
ON
•
Send
under
error
•
Receive
overrun error
INSTRUCT CODE ERROR
PARAMETER ERROR
MISSING END INS,
CAN'T EXECUTE (P)
S.~-
CHK FORMAT ERROR
diagnosis
RAM ERROR
error OPE. CIRCUIT ERROR ON
Lit
Flicker
ON
(Operation WDT ERROR
slop)
END NOT exECUTE
UNIT VERIFY ERROR (Stop)
FUSE BRERN OFF (Slop)
SP. UNIT ERROR (Slop)
ROM ERROR
Specification and external connection of the ERR terminals
Item
Speclflcetlon
Insulation method Photocoupler insulation
Rated load voltage 24 VAC
Operating load voltage range 10.2 to 31.2 VDC
Maximum load current 50 rnA
leak
current at OFF 0.1 rnA
Maximum
voltage
drop
at ON 1.5V (50 rnA)
-
ERR+
External connection
~~~
9
ER,~-
"
24VDC