4.A2CCPU
--------------------
MELSEC-A
4.2.5
Status latch
The monitoring function of a peripheral cannot confirm the status of each
I
device all
the
time. The status latch function transfers
and
saves
the
device
data to the status latch area when the
SlT
instruction is executed in the
sequence program.
The
device
data
saved
using
the
Sl
T
instruction
can
be read by
the
GPP/PHP/HGP to monitor it.
Status
latch
area
File
register
area
Device
memory
area
A2CCPU GPP/PHP/HGP
~-------------------------------,
r-----------------------------,
Transfer
I,
I
by
SlT
:Reading: 0"
If:
Instruction :in the PC: ISP't
ay
. or :
mode :
mom
onng :
+i,:
~~~~~s
...
<J~,:
area
, ,
, ,
, ,
, ,
, ,
, ,
, ,
, ,
L
~
Fig. 4.17
Status
Latch
Sequence
(1) Application
The status latch function can be used to check
the
device
data
when a t
fault condition exists during debugging. ,
It is also used to find causes when a fault condition exists
during
sequence program execution by making a program
that
will execute
the
Sl
T instruction if such a condition exists.
(2) Processing
(a) The following data is stored in
the
status latch area when
the
Sl
T
instruction is executed.
41
1) Device memory
X, Y, M,
l,
S, F, B ON/OFF data
T, C Contact and coil ON/OFF data and present
value
D, W, A, Z, V : Stored data
2) File register (R)
Stored data
4-28