4.A2CCPU
--------------------
MELSEC-A
4.1.6
Operation processing at momentary power failure
I
The A2C detects momentary power failure when
the
input
line voltage to the
power supply module falls below
the
defined range.
The A2C performs two different kinds of operation processing
depending
on
the
length of momentary power failure time across 20 msec allowable value.
(1) Momentary power failure within 20 msec
(a) The operation processing is
stopped
with the
output
retained.
(b) The operation processing resumed where normal status is restored.
(c) The watch
dog
timer (WDT) keeps timing while the operation is at a
stop. For instance, if
the
WDT and scan time settings are 200 msec
and 190 msec respectively, an momentary power failure of 20 msec
will result is a WDT error.
o
I
. Power recovery
Momentary power failure occurs.
(Sequence program continues.)
END 0 1 / END 0 END
I I
"\
i I I I
~ND
-+-----+-
'-------y'
Sequence
processing The A2C stops program
operation. operation
WDTtiming
Fig. 4.4
Momentary
Power
Failure
within
20
msec
(2) Momentary power failure over 20 msec
The A2C is reset. The A2C performs the initial start processing as it
does when it is turned on or reset by
the
RUN key switch operation.
oEND
Power failure (Initial start)
/0
'i I 1===11--
~Sequence
I L Initial program
. operation
processing
The A2C stops operation.
'--cE'ND
processing
Momentary power failure occurs.
END 0 j
I I •
Fig.
4.5
Momentary
Power
Failure
over
20
msec
4-9