2. SYSTEM CONFIGURATION
--------------------
MELSEC-A
2.2
Notes
on
System
Construction
(1) Connection of remote I/O modules and remote terminal modules
A maximum of 64 stations of remote I/O modules and remote terminal
modules can be connected to the A2C.
Also,
the
MINI-S3Iink disclose devices can be connected. (See Section
2.3.)
(2) Applicable remote terminal modules
I
A maximum of 14 remote terminal modules among those mentioned
below can be connected
to
the
A2C. However, when
the
AJ35PTF-R2
RS-232C interface module is used, up to 7 modules can be connected.
(a) A68ADC A/D conversion module
(b) A64DAVC D/A conversion module •
(c) A64DAIC D/A conversion module
(d) AD61C high speed
counter
module
(e) AJ35PTF-R2 RS-232C interface module (no-protocol mode only)
(3) Use of the MINI-S3 link modules
The following restrictions are applied when the MINI-S3 link remote I/O
..
modules
and
remote terminal modules are used.
..
(a) Twisted-pair data link
module:
No restriction is applied.
(b) Optical/twisted-pair data link
module:
When twisted-pair shield cables are used, no restriction is ap-
plied. •
When an optical data link module is used, use
this
module to
switch the twisted-pair shield cable data link with
the
fiber-optic
cable
data
link.
(c) Optical
data
link
module:
Usable when
the
optical/twisted-pair data link module is used as
the
optical data link module.
2-3