I
4.A2CCPU
--------------------
MELSEC·A
(b) Automatic online return
not
provided
In this mode, data communication is executed between
the
A2C and
a remote I/O module
and
remote terminal module.
II a communication error occurs with any
01
the
modules in
the
link,
data communication is executed only with modules operating cor-
rectly.
Once a module is disconnected
Irom
the
link, it cannot restart data
communications when it recovers normal operating state.
To restart data communication with a module disconnected
Irom
the
link,
turn
off
the
power to A2C
and
then
turn
it back on again or
reset it with the RUN key switch.
(c) Transmission
stop
at an occurrence
01
online error
1) II data communication error
occurs
with
anyone
01
the
stations
in the link, data communication stops over
the
entire link. •
To restart data communication in the link,
turn
off
the
power to
A2C
and
then turn it back on again or reset it with
the
RUN key
switch.
2) The setting
lor
the total
number
01 stations should be
the
last
station
number
01
remote I/O
modules
and
remote terminal
modules connected to the A2C.
If a
number
is greaterthan
the
last station number, such a station
is regarded as the
laulty
station precluding data communication.
(7) Remote terminal
The
remote terminal
setting
is necessary
to
use remote terminals
modules (up to
14
modules); the setting includes
the
station
number
and attribute.
(a) First station
number
The head station number (station number set with the station num-
ber
setting switch)
01
the remote terminal modules to be used
should be set
lor
the
station number.
(b) Protocol
Set attribute
lor
each remote terminal module.
•
1) Mitsubishi standard protocol (MINI protocol)
Setting
lor
remote terminal modules other
than
RS-232C inter-
lace
module (AJ35PTF-R2) should be
the
Mitsubishi standard
protocol.
2) No-protocol
Setting
lor
an RS-232C interlace module (AJ35PTF-R2) should •
be
the
no-protocol.
..
4-40