2. SYSTEM CONFIGURATION
--------------------
MELSEC-A
(7) If two or more I/O modules are connected to one power supply, choose
cables and wiring route considering voltage
drop
caused by cables.
The figure below explains
the
voltage
drop
caused by cables.
V2
I
I
/
\
I
,
0---)
Stabilized
/
power supply
11
+ 12
12
\
1/
1/
-,
I
Rl
R2
I I
I,
12
I
I/O module 1
I/O module
2
V1
Voltage drop between stabilized power supply and I/O module 1
V2 VoRage drop between I/O module 1 and I/O module 2
R1
Resistancebetween stabilized power supply and
110
module 1
R2 Resistance between
I/O
module 1 and I/O module 2
h Current consumption of I/O module 1
12
Current consumption of I/O module 2
!Voltage
drop
calculation
I
VI = Rl x
(11
+
12)
V2 = R2X
12
I
Receiving
port
voltage
of
I/O
module
I
(Receiving port voltage of I/O module 1)
= (Voltage of stabilized power supply) - VI
(Receiving port voltage of I/O module 2)
= (Voltage of stabilized power supply) - VI - V2
An I/O module can be connected if the receiving portvoltage of I/O module
is higher than
the
rated voltage of the I/O module
to
be used.
2-7
•