4.A2CCPU
-------------------
MELSEC-A
4:2.4
Stollplng
the
sequence program operation retaining outputs (PAUSEfunction)
The pause function
stops
A2CCPU operation while retaining
the
status of all I
outputs
(Y).
(1) Application
In
process
control, it is often required to retain
the
status of
the
outputs
(Y)
when
the
A2CCPU
stops
operating.
(2) Using remote PAUSE
contacts
(a) The PAUSE state
contacts
(M9041) close after
the
execution of
the
END(FEND) instruction of
the
scan
during
which
the
remote PAUSE
contacts
close and
the
PAUSE permission flag (M9040) is set.
When
the
END(FEND) instruction of
the
scan
after M9041 has set
is executed,
the
A2C is set to PAUSE and
its
operation
stops.
(b) By
opening
the
remote
PAUSE
contacts
or by switching
off
M9040
on a peripheral device,
the
PAUSE state is canceled,
and
sequence
program operation resumes from
step
O.
Remole PAUSE
contact
M9040
M9041
RUN/STOP state
0---
END
o
----END
ON
OFF
I
ON
OFF
I
ON
OFF
~edOnWhen
conditions to set the
PAUSE
CPU module In the
RUN
pause state are
satisfied
-
O-END
0-
--
--
--
•
PAUSE state
Fig.
4.15
PAUSE
Timing
by
the
Remote
PAUSE
Contact
4-26