B-39
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
5.4.16 BFM#71 to #74: Lower limit error setting / BFM#81 to #84: Upper limit error setting
Setting range: See below.
Initial value: See below.
Numeric data type: Decimal (K)
Set the upper/lower limit error data so that the upper/lower limit error status (BFM#26) can be detected.
The data setting range depends on the input mode set in BFM#0.
The following table shows the data setting range for each input mode:
1. Cautions regarding upper/lower limit error setting
To use the set upper/lower limit error data, be sure to turn on the upper/lower limit error detection function
(b1 of BFM#22).
To use the data addition function (b0 of BFM#22) together with this function, be sure to add the addition
data (channels 1 to 4: BFM#61 to #64) to the upper/lower limit values to be set. In addition, observe the
data setting range.
Input mode (BFM#0)
Setting range
Initial value
Set
value
Description
Lower limit value
(Channels 1 to 4:
BFM#71 to #74)
Upper limit value
(Channels 1 to 4:
BFM#81 to #84)
0
Voltage input
(-10 V to +10 V: -32000 to +32000)
-32768 to +32767 -32768 32767
1
Voltage input
(-10 V to +10 V: -4000 to +4000)
-4095 to +4095 -4095 4095
2
Voltage input
Analog value direct indication mode
(-10 V to +10 V: -10000 to +10000)
-10200 to +10200 -10200 10200
3
Current input
(4 mA to 20 mA: 0 to 16000)
-1 to +16383 -1 16383
4 Current input (4 mA to 20 mA: 0 to 4000) -1 to +4095 -1 4095
5
Current input
Analog value direct indication mode
(4 mA to 20 mA: 4000 to 20000)
3999 to 20400 3999 20400
6
Current input
(-20 mA to +20 mA: -16000 to +16000)
-16384 to +16383 -16384 16383
7
Current input
(-20 mA to +20 mA: -4000 to +4000)
-4096 to +4095 -4096 4095
8
Current input
Analog value direct indication mode
(-20 mA to +20 mA: -20000 to +20000)
-20400 to +20400 -20400 20400