EasyManua.ls Logo

Mitsubishi Electric MELSEC-FX3S Series - Selection of the Resistance Thermometer Sensor; Wiring of the Resistance Thermometer Sensor; Caution Regarding Wiring

Mitsubishi Electric MELSEC-FX3S Series
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
K-16
3 Wiring
3.4 Selection of the Resistance Thermometer Sensor
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
3.4 Selection of the Resistance Thermometer Sensor
Select the Pt1000/Ni1000 (2-wire or 3-wire sensors) resistance thermometer sensor.
3.5 Wiring of the Resistance Thermometer Sensor
Wiring depends on the resistance thermometer sensor type selected. Refer to the following wiring diagrams:
*1. For FX
3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
*2. When using a 2-wire temperature sensor type, short-circuit the [L -] terminal and the [I -] terminal.
For the lead wire use a 10 Ω resistance or less per line.
*3. Separate the cable of the platinum resistance thermometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
3.6 Caution Regarding Wiring
It is not possible to connect different types of resistance thermometer to 4 channels of PNK-ADP. Be sure
to use the same type of resistance thermometer for all the channels.
3.7 Grounding
Grounding should be performed as stated below.
The grounding resistance should be 100 Ω or less.
Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the User’s Manual - Hardware Edition of the each PLC Series.
The grounding wire size should be AWG22 to 20 (0.3 to 0.5 mm
2
).
The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
1M
ch
PNK-ADP
Class-D grounding
+5V
24+
24-
Shield wire
Terminal
block
24V DC
*1
L+, L-, I-, ch: represents the channel number.
3-wire
sensors
type
1M
47k47k
+5V
1M
ch
+5V
1M
47k47k
2-wire
sensors
type
L-
I-
L+
L-
I-
L+
*2
*3
Resistance thermometer
wiring
External power supply
wiring
PLCPLCPLC
Other
equipment
Other
equipment
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition

Table of Contents

Related product manuals