EasyManua.ls Logo

Mitsubishi Electric MELSEC-FX3S Series - Special Function Block; List of Analog Product Models

Mitsubishi Electric MELSEC-FX3S Series
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A-12
2 Description of Analog Products
2.2 List of Analog Product Models
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
2.2.3 Special function block
•FX3G/FX3GC/FX3U/FX3UC Series PLC
Type
No. of
channels
Range Resolution Function
Refer-
ence
Voltage/current input
FX
3U-4AD
*1
4ch
Voltage:
-10 V to +10 V DC
0.32 mV
(with sign, 16 bits)
Combined use of voltage and
current inputs is possible.
The
offset/gain can be adjusted
.
*3
The sampling function is
incorporated.
B
Current:
-20 mA to +20 mA DC
1.25 μA
(with sign, 15 bits)
FX
3UC-4AD
*2
4ch
Voltage:
-10 V to +10 V DC
0.32 mV
(with sign, 16 bits)
Combined use of voltage and
current inputs is possible.
The
offset/gain can be adjusted
.
*3
The sampling function is
incorporated.
B
Current:
-20 mA to +20 mA DC
1.25 μA
(with sign, 15 bits)
FX
2NC-4AD
*2
4ch
Voltage:
-10 V to +10 V DC
0.32 mV
(with sign, 16 bits)
Combined use of voltage and
current inputs is possible.
The offset/gain can be
adjusted.
*3
The sampling function is
incorporated.
*5
Current:
-20 mA to +20 mA DC
1.25 μA
(with sign, 15 bits)
FX
2N-8AD
*1
8ch
Voltage:
-10 V to +10 V DC
0.63 mV
(with sign, 15 bits)
Combined use of voltage,
current, and thermocouple is
possible.
The offset/gain can be
adjusted
.
*3
The sampling function is
incorporated.
*5
Current:
-20 mA to +20 mA DC
2.5 μA
(with sign, 14 bits)
FX
2N-4AD
*1
4ch
Voltage:
-10 V to +10 V DC
5 mV
(with sign, 12 bits)
Combined use of voltage and
current inputs is possible.
The offset/gain can be adjusted.
*5
Current:
-20 mA to +20 mA DC
10 μA
(with sign, 11 bits)
FX
2N-2AD
*1
2ch
Voltage:
0 V to 10 V DC
2.5 mV
(12 bits)
Combined use of voltage and
current inputs is impossible.
The offset/gain can be adjusted.
(Common to 2 input channels)
*5
Current:
4 mA to 20 mA DC
4 μA
(12 bits)
Voltage/current output
FX
3U-4DA
*1
4ch
Voltage:
-10 V to +10 V DC
0.32 mV
(with sign, 16 bits)
Combined use of voltage and
current outputs is possible.
*4
The offset/gain can be adjusted.
E
Current:
0 mA to 20 mA DC
0.63 μA
(15 bits)
FX
2NC-4DA
*2
4ch
Voltage:
-10 V to +10 V DC
5 mV
(with sign, 12 bits)
Combined use of voltage and
current outputs is possible.
The offset/gain can be adjusted.
*5
Current:
0 mA to 20 mA DC
20 μA
(10 bits)
FX
2N-4DA
*1
4ch
Voltage:
-10 V to +10 V DC
5 mV
(with sign, 12 bits)
Combined use of voltage and
current outputs is possible.
The offset/gain can be adjusted.
*5
Current:
0 mA to 20 mA DC
20 μA
(10 bits)
FX
2N-2DA
*1
2ch
Voltage:
0 V to 10 V DC
2.5 mV
(12 bits)
Combined use of voltage and
current outputs is possible.
The offset/gain can be adjusted.
*5
Current:
4 mA to 20 mA DC
4 μA
(12 bits)
*1. To connect this block to the FX3GC/FX3UC Series PLC, either the FX2NC-CNV-IF or FX3UC-1PS-5V is
required.
*2. Connectable with the FX
3GC/FX3UC Series PLC only.
*3. The offset and gain of the FX
3U-4AD, FX3UC-4AD, FX2NC-4AD and FX2N-8AD cannot be adjusted for
channels using the analog value direct indication mode.
*4. The offset and gain of the FX
3U-4DA cannot be adjusted for channels using the analog value mV (or μA)
specification mode.
*5. Refer to the instruction manual of the respective product.

Table of Contents

Related product manuals