A-40
4 Comparison of Performance Specifications
4.2 Analog Output
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
4.2.6 FX3G-1DA-BD
Specifications
FX3G-1DA-BD
Voltage output Current output
Number of output points 1ch
Analog output range
0V to 10V DC
(External load: 2 k to 1 MΩ)
4mA to 20mA DC
(External load: 500 Ω or less)
Offset
Impossible to change Impossible to change
Gain
Digital input 12 bits, binary 11 bits, binary
Resolution
2.5mV (10V × 1/4000) 8μA (16mA × 1/2000)
Overall accuracy
Ambient temperature:
25±5°C
±0.5% (±50mV) for 10V full scale ±0.5% (±80μA) for 16mA full scale
Ambient temperature:
0 to 55°C
±1.0% (±100mV) for 10V full scale ±1.0% (±160μA) for 16mA full scale
Reference
Shipment adjustment is carried out by external
load resistance 2 kΩ.
If external load resistance becomes larger than
2 kΩ, the output voltage will increase slightly.
When the load is 1 MΩ, the output voltage is
about 2% higher than the correct value.
-
Time required for D/A
conversion
60μs (Data updated every scan time.)
Output characteristics
Caution:
An area of dead band is located in the region of
0V. Therefore the output analog value may not
represent the digital value accurately.
Insulation method • The analog output area is not insulated from the PLC.
Number of I/O points
occupied
0 point (This number is not related to the maximum I/O points of the PLC.)
0
10V
4000 4080
Digital input
Analog output
0
2000
20mA
Digital input
Analog output
4mA
2040