A-40
4 Comparison of Performance Specifications
4.2 Analog Output
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
4.2.6 FX3G-1DA-BD
Specifications
FX3G-1DA-BD
Voltage output Current output
Number of output points 1ch
Analog output range
0V to 10V DC
(External load: 2 k to 1 MΩ)
4mA to 20mA DC
(External load: 500 Ω or less)
Offset
Impossible to change Impossible to change
Gain
Digital input 12 bits, binary 11 bits, binary
Resolution
2.5mV (10V × 1/4000) 8μA (16mA × 1/2000)
Overall accuracy
Ambient temperature:
25±5°C
±0.5% (±50mV) for 10V full scale ±0.5% (±80μA) for 16mA full scale
Ambient temperature:
0 to 55°C
±1.0% (±100mV) for 10V full scale ±1.0% (±160μA) for 16mA full scale
Reference
Shipment adjustment is carried out by external
load resistance 2 kΩ.
If external load resistance becomes larger than
2 kΩ, the output voltage will increase slightly.
When the load is 1 MΩ, the output voltage is
about 2% higher than the correct value.
-
Time required for D/A
conversion
60μs (Data updated every scan time.)
Output characteristics
Caution:
An area of dead band is located in the region of
0V. Therefore the output analog value may not
represent the digital value accurately.
Insulation method The analog output area is not insulated from the PLC.
Number of I/O points
occupied
0 point (This number is not related to the maximum I/O points of the PLC.)
0
10V
4000 4080
Digital input
Analog output
0
2000
20mA
Digital input
Analog output
4mA
2040