PLC User's Manual - Analog Control Edition
FX
3U
-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
2.4.3 When connected to a FX3U/FX3UC PLC
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers.
2. A/D conversion during PLC stop
Even if the PLC is stopped, A/D conversion will be performed and the special data registers will be updated.
3. If two or more analog special adapters are connected
During execution of the END instruction, data will be read out from all the connected adapters (in the order of
1st adapter → 2nd adapter … 4th adapter).
4. A/D conversion speed (data update time)
During execution of the END instruction, the A/D converted data of all 4 channels will be read out in 200 μs,
and the data read out will be written to the special data registers.
END instruction execution time will be "200 μs × number of connected adapters."
2.5 Temperature Measurement
To stabilize the temperature measurement, warm-up the system for 30 minutes or more after power-on.
FX3U/FX3UC Series PLC
FX3U-4AD-PT-ADP
1st
FX3U-4AD-PT-ADP
n'th
A/D
conversion
200 s/4ch
A/D
conversion
200 s/4ch
Digital value reading
A/D conversion start
command
A/D conversion start
command
END instruction
Sequence
program
Digital value reading