D-8
2 Specifications
2.2 Performance Specifications
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3G-2AD-BD (2-channel Analog Input)
2.2 Performance Specifications
Item
Specifications
Voltage input Current input
Analog input
range
0V to 10V DC
(Input resistance: 198.7 kΩ)
4mA to 20mA DC
(Input resistance: 250 Ω)
Absolute input
maximum
-0.5V, +15V -2mA, +30mA
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV (10V/4000) 8μA (16mA/2000)
Total accuracy
±0.5% (±50mV) for 10V full scale
(when ambient temperature is 25°C ± 5°C)
±1.0% (±100mV) for 10V full scale
(when ambient temperature is 0°C to 55°C)
±0.5% (±80μA) for 16mA full scale
(when ambient temperature is 25°C ± 5°C)
±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0°C to 55°C)
A/D conversion
time
180 μs (The data will be updated at every scan time.)
For a detailed description of data update, refer to Section 2.3.
Input
characteristics
Insulation method
The analog input area is not insulated from the PLC.
Channels are not insulated from each other.
Number of I/O
points occupied
0 point (This number is not related to the maximum number of input/output points of the PLC.)
0
4000
10V
10.2V
4080
Analog input
Digital output
0
2000
20mA
20.32mA
2040
Analog input
Digital output
4mA

Table of Contents