3.5 Grounding
Grounding should be performed as stated below.
The grounding resistance should be 100 Ω or less.
Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the User's Manual - Hardware Edition of the each PLC Series.
The grounding wire size should be AWG22 to 20 (0.3 to 0.5 mm
2
).
The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
PLCPLCPLC
Other
equipment
Other
equipment
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition