PLC User's Manual - Analog Control Edition
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
K
FX
3U
-4AD-PNK
-ADP
L
FX
3U
-4AD-TC
-ADP
M
PID Instruction
(FNC 88)
1. Outline
This chapter describes the outline of FX3U-4AD-PNK-ADP (referred to as PNK-ADP).
1.1 Outline of Functions
The FX3U-4AD-PNK-ADP is an analog special adapter. Connect the FX3U-4AD-PNK-ADP to the FX3S/FX3G/
FX
3GC/FX3U/FX3UC Series PLC to read the data from the 4-channel resistance thermometer.
1) Only 1 PNK-ADP unit can be connected to the FX
3S Series PLC.
Up to 2
*1
PNK-ADP units can be connected to the FX3G/FX3GC Series PLC.
Up to 4 PNK-ADP units can be connected to the FX
3U/FX3UC Series PLC.
(including the other analog expansion boards, analog special adapters)
2) Thermometer types Pt1000 and Ni1000 can be connected. (However, it's impossible to use both types
Pt1000 and Ni1000 with 1 adapter.)
3) The temperature data will be automatically written to the special data register of the FX
3S/FX3G/FX3GC/
FX
3U/FX3UC Series PLC.
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of
connectable units and to configure the entire system.
*1. Only 1 analog special adapter can be connected to the FX
3G Series PLC (14-point and 24-point type).
*2. The expansion board is not required when connecting with the FX
3GC/FX3UC (D, DS, DSS) Series PLC.
For the FX
3S/FX3G Series PLC a connector conversion adapter is used.
*3. FX
3S/FX3G/FX3GC PLCs use the following special devices.
For FX
3S Series PLC For FX3G/FX3GC Series PLC
• 1st adapter: M/D8280 to M/D8289 • 1st adapter: M/D8280 to M/D8289
• 2nd, 3rd and 4th adapters: Cannot be connected • 2nd adapter: M/D8290 to M/D8299
• 3rd and 4th adapters: Cannot be connected
Number of connectable
units
For a detailed
description of wiring,
refer to Chapter 3.
To check the connectable
PLC model number, refer
to Section 1.3.
Point and section to be referred to
System
Special devices
*3
For a detailed description
of special devices, refer to
Chapter 4.
For a detailed description
of a basic program, refer to
Section 4.9.
Analog data
FX
3S
Series PLC : Only 1
FX
3G
/FX
3GC
Series PLC : 2
*1
maximum
FX
3U
/FX
3UC
Series PLC : 4 maximum
including the other analog expansion
boards, analog special adapters
1st adapter
M/D8260 to M/D8269
M/D8270 to M/D8279
M/D8280 to M/D8289
M/D8290 to M/D8299
2nd adapter
3rd adapter
4th adapter
+
+
Expansion
board
*2
FX3U/FX3UCFX3S/FX3G/FX3GC/
For FX
3S/FX3G/FX3GC/
FX
3U/FX3UC
Series PLC
4th
adapter
3rd
adapter
2nd
adapter
1st
adapter
Transfer direction
Description
Resistance thermometer sensor type
Pt1000 and Ni1000
Temperature measurement
Setting of temperature unit
Switching of types between
type Pt1000 and Ni1000
Setting of averaging time
Series PLC