198
6 OPTIONS AND PERIPHERAL EQUIPMENT
6.9 Selection example of wires
Wire size selection examples
Use 600 V Grade heat-resistant polyvinyl chloride insulated wires (HIV wires) for wiring. The following shows the wire size
selection examples.
■200 V class
*1 Use the size of 2 mm
2
for compliance with the IEC/EN/UL/CSA standard.
*2 The wire size shows applicable size of the servo amplifier connector and terminal block. For wires connecting to the servo motor, refer to
the user's manual of each servo motor.
■Using servo amplifier with DC power supply input
The wire selection example is the same as that for the AC power supply input.
Selection example of crimp terminals
■200 V class
• Crimp terminals are used only for ground wiring.
Servo amplifier Wire [mm
2
]
(1) L1/L2/L3/ (2) L11/L21 (3) P/C (4) U/V/W/E
MR-J5-10_ 2 (AWG 14): a 1.25 to 2 (AWG 16 to 14)
*1
2 (AWG 14) AWG 18 to 14
MR-J5-20_
MR-J5-40_
MR-J5-60_
MR-J5-70_
MR-J5-100_
MR-J5-200_
(3-phase power supply input)
AWG 18 to 10
MR-J5-200_
(1-phase power supply input)
3.5 (AWG 12): b
MR-J5-350_
MR-J5-500_ 5.5 (AWG 10): c AWG 18 to 8
MR-J5-700_ 8 (AWG 8): d
MR-J5W2-22G_ 2 (AWG 14): a 2 (AWG 14) AWG 18 to 14
MR-J5W2-44G_
MR-J5W2-77G_ 2 (AWG 14): a
MR-J5W2-1010G_ 2 (AWG 14): a
MR-J5W3-222G_ 2 (AWG 14): a
MR-J5W3-444G_ 2 (AWG 14): a
Symbol Servo amplifier-side crimp terminal Manufacturer
Crimp terminal Applicable tool
a R2-4 YHT-2210 JST (J.S.T. Mfg. Co., Ltd.)
b 3.5-4 YHT-2210
c R5.5-4 YHT-2210
d 8-4NS, R8-5 YHT-8S, YA-4