6 OPTIONS AND PERIPHERAL EQUIPMENT
6.10 Molded-case circuit breakers, fuses, magnetic contactors
Related supplementary information
■Permissible current of wire
The following table shows permissible currents of wire based on Table 28.1 of UL 508A and Table 40.3 of UL 508C.
The permissible current values listed in this table are for when the number of wires bundled is three or less. When the number
of wires bundled is four to six, the permissible current values are 80 % of the values in the table.
• Permissible currents of copper wire (insulated conductor)
■Rated input current of servo amplifier
The following table shows the 3-phase rated input currents and maximum wire sizes for the MR-J5 series.
• 3-phase rated input currents, inrush currents, and maximum wire sizes for servo amplifiers
■Molded-case circuit breakers (MCCB) and magnetic contactors (MC)
The following tables show lists of rated currents for the Mitsubishi Electric UL 489 Listed molded-case circuit breakers and for
magnetic contactors.
• List of rated currents for molded-case circuit breakers (MCCB)
*1 For molded-case circuit breakers that support the current values enclosed in brackets "( )" in the rated current column, contact your local
sales office.
• List of rated currents for magnetic contactors (MC)
Wire size 60 °C (140 °F) 75 °C (167 °F)
AWG Actual cross-sectional
area [mm
2
]
Nominal cross-
sectional area [mm
2
]
[A] [A]
14 2.1 2 15 15
12 3.3 3.5 20 20
10 5.3 5.5 30 30
88.484050
613.3145565
421.2227085
233.63895115
142.4 110 130
Model Input current [A] Inrush current [A] Maximum AWG
MR-J5-10_ 0.9 17 14
MR-J5-20_ 1.5 17 14
MR-J5-40_ 2.6 17 14
MR-J5-60_ 3.2 17 14
MR-J5-70_ 3.8 17 14
MR-J5-100_ 5 17 14
MR-J5-200_ 10.5 24 14
MR-J5-350_ 16 85 12
MR-J5-500_ 21.7 42 10
MR-J5-700_ 28.9 85 8
MR-J5W2-22G_ 2.9 23 14
MR-J5W2-44G_ 5.2 23 14
MR-J5W3-222G_ 4.3 23 14
MR-J5W3-444G_ 7.8 23 14
MR-J5W2-77G_ 7.5 36 14
MR-J5W2-1010G_ 9.8 36 14
Model Rated voltage AC [V] Rated current [A]
*1
NF125-SVU 480 15, 20, 30, 40, 50, 60, (70), 75, (80), (90), 100, 125
MS-T series Frame T10 T12 T20 T21 T25 N35 N50 N65 N80 N125
AC3 class [kW/A] 220 V 2.2 2.7 3.7 4 5.5 7.5 11 15 19 30
440 V 2.7 4 7.5 7.5 11 15 22 30 37 60
Thermal current [A] 20202032326080100120150