104
3 SPECIFICATIONS
3.3 Performance Specifications
NZ2GN12A42-16DTE DC input/transistor output module
Item NZ2GN12A42-16DTE
Input specifications
Number of input points 8 points
Rated input voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Rated input current 7.3mA TYP. (for 24VDC)
Maximum number of simultaneous input points 100%
ON voltage/ON current 11VDC or more/4mA or more
OFF voltage/OFF current 5VDC or less/1.5mA or less
Input resistance 3.0k
Input response time OFF ON 0ms
*1
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Factory default: 10ms)
ON OFF
Wiring method for common 8 points/common (2- to 4-wire, waterproof connector type)
Negative common type
Current supplied to external devices 0.4A/terminal
Output specifications
Number of output points 8 points
Rated load voltage 12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Max. load current 4A/point (Y8 to YB)
*2
, 2A/point (YC to YF), 12A/common
Maximum inrush current Current is limited by the overload protection function.
Leakage current at OFF 0.1mA or less
Max. voltage drop at ON 0.3VDC (TYP.) 2A, 0.6VDC (MAX.) 2A, 0.6VDC (TYP.) 4A, 1.2VDC (MAX.) 4A
Output response time OFF ON 0.5ms or less
ON OFF 1.0ms or less (resistive load)
Surge suppressor Zener diode
External power supply for
output part
*4
Voltage 12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current 30mA or less (TYP. 24VDC per common) External load current is not included.
Protection function Overload protection
function
Limited current when detecting overcurrent: 5.2A or more/point
Activated to each point.
Overheat protection
function
Activated to each point.
Wiring method for common 8 points/common (2-wire, waterproof connector type)
Source type
Common specifications
Station type Remote station
Authentication Class Authentication Class B
Network topology Line topology, star topology, mixture of star topology and line topology, ring topology
Withstand voltage 720VDC for 1 minute between all DC external terminals and ground
Insulation resistance 10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree IP67
External interface Communication part M12 waterproof connector, 8 pins, female, X-code
Module power supply part M12 waterproof connector, 5 pins, male, female, L-code
I/O part M12 waterproof connector, 5 pins, female, A-code
Applicable waterproof
connector
For communications Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
For power supply
For I/O
Y-branch connector for I/O
Multicast filter Available
Cyclic transmission RX/RY points 16 points
RWr/RWw points 4 points
*3
Module power supply
*4
Voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current 160mA or less (24VDC, all points ON)

Table of Contents