20
3 SPECIFICATIONS
3.1 General Specifications
I/O module (waterproof module)
*1 Only when all necessary waterproof connectors and caps have been installed and the indicator cover for the IP address/station number
setting switches and the function setting switches has been properly tightened with screws, the module is compliant with IP67. For the
tightening torque range of the cover screws for the switches, refer to the following.
Page 117 Indicator cover of the I/O module (waterproof module),Page 150 Attaching Waterproof Caps
*2 Do not use or store the I/O module (waterproof module) under pressure higher than the atmospheric pressure of altitude 0m. Doing so
may cause malfunction.
*3 If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the module can be
used even outside the control panel.
*4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises. Category applies to equipment for which electrical power is supplied from
fixed facilities. The surge voltage withstand level for the equipment with the rated voltage of 300V or less is 2500V.
*5 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
For compliance with the EMC Directive, refer to the following:
Page 246 EMC and Low Voltage Directives
Item Specifications
Operating ambient temperature 0 to 55
Storage ambient temperature -25 to 75
Operating ambient humidity Compliant with IP67
*1
Storage ambient humidity 5 to 95%RH, non-condensing
Vibration resistance Compliant with JIS
B 3502 and IEC
61131-2
Frequency Constant
acceleration
Half amplitude Number of sweeps
Under intermittent
vibration
5 to 8.4Hz 3.5mm 10 times each in X,
Y, and Z directions
8.4 to 150Hz 9.8m/
Under continuous
vibration
5 to 8.4Hz 1.75mm
8.4 to 150Hz 4.9m/
Shock resistance Compliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z directions)
Operating atmosphere No corrosive gases, flammable gases, less conductive dust
Operating altitude
*2
0 to 2000m
Installation location Inside a control panel
*3
Overvoltage category
*4
or less
Pollution degree
*5
2 or less
Equipment class Class