3 SPECIFICATIONS
3.3 Performance Specifications
59
3
NZ2GNCF1-32T transistor output module
*1 The performance specifications vary depending on firmware versions of modules used. ( Page 256 Added and Changed Functions)
*2 Use bar solderless terminals for wiring.
*3 Only one wire can be inserted into a wire insertion opening for the terminal block for module power supply and FG. Multiple wires cannot
be connected to a terminal. Connecting two or more wires may cause a poor contact.
*4 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 227 Output module (32-
point module))
Item NZ2GNCF1-32T
Station type Remote station
Authentication Class Authentication Class B
Network topology Line topology, star topology, mixture of star topology and line topology, ring topology
*1
Number of output points 32 points
Rated load voltage 12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Max. load current 0.1A/point, 3.2A/common
Maximum inrush current Current is limited by the overload protection function.
Leakage current at OFF 0.1mA or less
Max. voltage drop at ON 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A
Output response time OFF ON 0.1ms or less
ON OFF 0.8ms or less (resistive load)
Surge suppressor Zener diode
External power supply for
output part
Voltage 12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current 40mA or less (TYP. 24VDC per common) External load current is not included.
Withstand voltage 510VAC for 1 minute between all DC external terminals and ground
Insulation resistance 10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree IP2X
Wiring method for common 32 points/common (Common terminal: pin number A1, A2) (1-wire, 40-pin connector type)
Sink type
Protection function Overload protection
function
Limited current when detecting overcurrent: 1 to 3A/point
Activated to each point.
Overheat protection
function
Activated to each point.
External interface Communication part RJ45 connector
Module power supply part Terminal block for module power supply and FG (2-piece spring clamp terminal block)
I/O part 40-pin connector
Applicable wire size For power supply Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm 1.5mm
*2
For I/O 40-pin connector
The size depends on the connector plug used (sold separately). ( Page 141 Wiring of 40-pin
connector)
Applicable solderless
terminal
*3
Terminal block for module
power supply and FG
Page 127 Applicable solderless terminal
Multicast filter Available
*1
Cyclic transmission RX/RY points 32 points
RWr/RWw points 4 points
*4
Module power supply Voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current 120mA or less (24VDC, all points ON)
Weight 0.16kg