3 SPECIFICATIONS
3.3 Performance Specifications
77
3
NZ2GN12A2-16TE transistor output module
*1 Make sure that the total amount of output current that flows through one connector is 4A or less.
*2 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 226 Output module (16-
point module))
*3 For a power supply to be connected to the waterproof I/O module (such as the module-and-sensor power supply or the load power
supply and external power supply for output part), use the power supply that meets the following condition.
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
Item NZ2GN12A2-16TE
Station type Remote station
Authentication Class Authentication Class B
Network topology Line topology, star topology, mixture of star topology and line topology, ring topology
Number of output points 16 points
Rated load voltage 12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Max. load current 4A/point (Y0 to Y3)
*1
, 2A/point (Y4 to YF), 12A/common
Maximum inrush current Current is limited by the overload protection function.
Leakage current at OFF 0.1mA or less
Max. voltage drop at ON 0.3VDC (TYP.) 2A, 0.6VDC (MAX.) 2A, 0.6VDC (TYP.) 4A, 1.2VDC (MAX.) 4A
Output response time OFF ON 0.5ms or less
ON OFF 1.0ms or less (resistive load)
Surge suppressor Zener diode
External power supply for
output part
*3
Voltage 12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current 45mA or less (TYP. 24VDC per common) External load current is not included.
Withstand voltage 720VDC for 1 minute between all DC external terminals and ground
Insulation resistance 10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
Protection degree IP67
Wiring method for common 16 points/common (2-wire, waterproof connector type)
Source type
Protection function Overload protection
function
Limited current when detecting overcurrent: 5.2A or more/point
Activated to each point.
Overheat protection
function
Activated to each point.
External interface Communication part M12 waterproof connector, 8 pins, female, X-code
Module power supply part M12 waterproof connector, 5 pins, male, female, L-code
I/O part M12 waterproof connector, 5 pins, female, A-code
Applicable waterproof
connector
For communications Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
For power supply
For I/O
Y-branch connector for I/O
Multicast filter Available
Cyclic transmission RX/RY points 16 points
RWr/RWw points 4 points
*2
Module power supply
*3
Voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current 110mA or less (24VDC, all points ON)
Weight 0.42kg