7.1.2.2 Controller Settings of Screen Design Software
Item
Set Value
Remarks
GOT NET No.
1
GOT Station
18
GOT Communication Port No..
5001
Retry (Times)
3
Startup Time (Sec)
3
Timeout Time (Sec)
3
Delay Time (ms)
0
GOT Ethernet Setting
Item
Set Value
Remarks
Update GOT Ethernet Standard Port
Setting
Checked
GOT IP Address
192.168.3.18
Subnet Mask
255.255.255.0
Default Gateway
0.0.0.0
Peripheral S/W Communication Port No.
5015
Transparent Port No..
5014
7.1.3 Ethernet Controller Settings of Screen Design Software
Host
Net No.
Station
Unit Type
IP Address
Port No.
Communication
1
*
1
1
RCPU *1
192.168.3.39
5006
UDP
*1: Change the models according to the CPU in use.
QCPU: QnUD(P)V/QnUDE(H)
LCPU : LCPU
7.1.4 Routing Information Settings
Routing information settings is required in order to connect to a different network. Set as below.
Transfer Net No.
Relay Net No.
Relay Station No.
CH1
2
1
1
7.1.5 PLC Side Settings (GX Works3)
(1) Go to [Parameter]-[Module Information] and add RJ71EN71.
[RJ71EN71(E-E)] - [Port 1 Module Parameter (Ethernet)] - [Basic Settings] - [Own Node Settings]
Item
Set Value
Remarks
IP Address
192.168.3.40
Ethernet unit IP address
Communications by
Network No./Station No.
Enable
Setting Method for Network No. and
Station Number
Not Use IP Address
Network No.
2
Station Number
40
(2) Go to [Parameter] - [Module Information] - [RJ71EN71(E-E)] - [Port 1 Module Parameter(Ethernet)] -
[Application Settings] - [Network Station No. <-> IP Information] and set the destination network number,
station number, and IP address.*1
Network No.
Station
IP Address
Remarks
2
40
192.168.3.40
Set the Ethernet module’s station number and
IP address.
2
1
192.168.3.50
Set the inverter’s station number and IP
address*2.
*1: For QCPU and LCPU, go to [Parameter] - [Network Parameter (Ethernet/CC IE Field)] in GX Works2 and
add Ethernet to the module 1, and apply the settings above under [Station No. <-> IP Information].
*2: Apply settings to all the connected inverters.
For detail, please refer to the users manual of the devices in use.