Press the SET key to determine the set value.
The set value and parameter number are displayed alternately, and the setting is completed.
4 Setting the parameter Pr. 332 to "192"
("192" indicates the baud rate of 19200 bps.)
Turn the setting dial until "Pr. 332" is displayed.
Press the SET key to read the current set value.
Turn the setting dial, and change the set value to "192".
Press the SET key to determine the set value.
The set value and parameter number are displayed alternately, and the setting is completed.
5 Changing other parameters in the same way as step 4
→ For details on the parameters to be set, refer to Subsection 5.6.1.
The set value and parameter number are displayed alternately.