• From the Programmable controller to the LE - 40MTB-E 
By turning on and off the internal contacts M800 to M806 on the programmable controller side, the 
contact command inputs MC1 to MC6 in the LE-40MTB-E can be operated. The OR command is 
entered  in the input terminals in the LE-40MTB-E. The M807 is used to transfer the data devices.
• From the LE-40MTB-E to the programmable controller
By monitoring the internal contacts M900 to M906 on the programmable controller side, the I /O 
status of the contacts in the LE-40MTB-E can be monitored. The M907 is used to transfer the data 
devices.
 
( Example of program )
Device No. Set item Device No. Monitor item
M800 MC1 M900 MC1
M801 MC2 M901 MC2
M802 MC3 M902 MC3
M803 MC4 M903 MC4
M804 MC5 M904 MC5
M805 MC6 M905 MC6
M806 MANUAL/AUTO M906 ZT
M807
Sending to word 
data is completed.
M907
Sending to word 
data is completed.
6. Linking the contact devices
M8000
X000
M906
[ M8070 ]
( M800 )
( Y000 )
Master station
Operation is started when X0 is turn ON (MC1=ON).
Emergency stop occurs when ZT is turned 
ON.