EasyManua.ls Logo

Moeller EC4-200 - Temperature Sensor; 20 Ma Sensor

Moeller EC4-200
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
05/06 AWB2724-1584GB
Connecting analog inputs
19
Temperature sensor 20 mA sensor
A 4 to 20 mA (0 to 20 mA) sensor can be connected easily with an
external 500 O resistor.
The following values apply:
4 mA = 1.9 V
10 mA = 4.8 V
20 mA = 9.5 V
(according to U = R x I = 478 O x 10 mA ~ 4.8 V)
Figure 17: Temperature sensor
+24 V H
0 V
Out
0...10 V
35...55 ˚C
+24 V H
0 V
Out
0...10 V
35...55 ˚C
L01
L01
I724 V 0 V
F1
I60 V I2I1 I4I3 I5 I8 I10I9 I12I11 0 V
Figure 18: 20 mA sensor
a Analog sensor
L01
F1
L01
a
500 O
4...20 mA
I724 V 0 V0 V I2I1 I4I3 I6I5
...