Operation
05/06 AWB2724-1584GB
46
X Change over to the Task configuration and open the “System
Events” folder.
X Enable IO-Interrupt 3 by clicking in the check box on the left
beside the name “IO-Interrupt 3”. The box is checked to
indicate that it has been activated.
X Select the area of the “Called POU” are and the line
“IO-Interrupt 3”.
X Set the cursor on the selected area and press the function
key F2.
The “Input Assistant” window is opened. This lists all the
predefined programs:
X Select the “Fastprog” POU and confirm with OK.
X Save the project. You can now test it.
The variable “b” is incremented by one with every rising edge on
input I3.
Generating and transferring a boot project
The CPU processes the user program stored in the main memory.
As the working memory is not backed up, the program will be lost
in the event of a power failure. You can therefore create a boot
project to store the program retentively.
You can generate the boot project in online mode or via the menu
of the controller. The boot program is generated with the current
operating system of the controller!
In online mode, the following steps are required:
X From the “Online menu”, select “Login”.
X If the controller is in the RUN state, you will be requested to
stop it.
X Select the “Create boot” project command.
Figure 46: Interrupt edge selection
Figure 47: Enabling an interrupt
Figure 48: Assignment of interrupt source l POU
Figure 49: Saving the boot project
Main memory Program
Create boot project
System memory Boot project
Browser: copyprojtommc
Memory card Boot project