Technical data
Climatic environmental conditions (Cold to IEC 60068-2-1, Heat
to IEC 60068-2-2)
Ambient temperature
Installed horizontally/vertically
°C, (°F) –25 to 55, (–13 to 131)
Condensation Prevent condensation with suitable measures
LCD display (reliably legible) °C, (°F)
0 to 55, (–32 to 131)
Storage/transport temperature °C, (°F)
–40 to 70, (–40 to 158)
Relative humidity (IEC 60068-2-30), non-condensing %
5 bis 95
Air pressure (operation) hPa
795 bis 1080
Ambient mechanical conditions
Degree of protection (IEC/EN 60529) IP20
Vibrations (IEC/EN 60068-2-6)
Constant amplitude 3.5 mm Hz 5 bis 9
Constant acceleration, 1 g Hz
9 bis 150
Shock (IEC/EN 60068-2-27)
Sinusoidal 15 g/11 ms
Shocks
18
Drop (IEC/EN 60068-2-31) Drop
height
mm 50
Free fall, packaged (IEC/EN 60068-2-32) m
1
Mounting position horizontal,vertical
Electromagnetic Compatibility (EMC)
Electrostatic discharge (ESD), (IEC/EN 61000-4-2, severity level 3)
Air discharge kV 8
Contact discharge kV
6
Electromagnetic fields (RFI), (IEC/EN 61000-4-3) V/m
10
Radio interference suppression
Limit value class
EN 55011, EN 55022
Class B
Fast transient burst (IEC/EN 61000-4-4, severity level 3)
Power cables kV 2
Signal cables kV 2
Surge
(IEC/EN 61000-4-5, degree of severity 2)
kV
0.5 symmetrical
1 asymmetrical
Immunity to line-conducted interference to (IEC/EN
61000-4-6)
V
10
Insulation resistance
Clearance and creepage distances EN 50178
Dielectric strength EN 50178
Overvoltage category/degree of pollution II/2