- 9 -
User’s Manual
225-748-00P
August 2024
Programmable RTD, T/C, Ohms, mV and Potentiometer Safety Trip Alarm
STA
TPRG
SECTION 1
POWER
U
Accepts any power input range between 21.6-375Vdc or 90-260Vac. Power consumption
is 3.5W maximum.
24DC*
This option instrument requires power is 24Vdc, ±25%. Power consumption is 3.5W
maximum.
UAC*
Accepts any power input range between 90-260Vac. Power consumption is 4W maximum.
*Power supply option no longer available for purchase.
OPTIONS
-AO
If your STA has the Analog Output option, Analog Output can be configured to provide
a voltage (0-10V) or current (0-20mA) output. The current output can be sink or
source. Refer to the Configuring the Analog Output section of this manual for additional
information.
Note: For units with firmware V1.2 or earlier, the Analog Output cannot be used as part of the
safety path.
HOUSING
[DIN]
DIN-style housing mounts on 35mm Top Hat rail (EN50022).
[FLB]
Flange bracket provides a secure mount for high vibration applications.