E09 E09
Evaporator fan motor
locked
4
ON
When a fan motor speed of
50 rpm or less is detected
four times within 10 seconds
after the fan motor is started.
OL OL Compressor overload
When compressor overload
relay is activated.
E11 E11
STI module
communication error
When a communication
failure between the STI
module and microcomputer
on the relay board is detected
for at least 40 seconds.
E12
E14
Compressor input over
current
When excessive current from
the STI module to the
compressor is detected.
E15
Compressor lock
failure
When the compressor motor is
locked and its operational
checking detects no change in
the compressor rotation position.
E16
Compressor phase
interruption abnormality
When one phase is detected
as 0 A.
E17
Motor position
detection abnormality
When an abnormality in the
compressor motor rotation
position is detected.
E13
E18
STI module input over
current
When excessive current from
the power source to the STI
module is detected.
E19
Power device
temperature
abnormality
When STI module
temperature that exceeds the
specified value is detected.
E20
DC voltage
abnormality
When a DC voltage or current
that is at or below the specified
value, or at or above the
specified value is detected.
E21
Power device damage
abnormality
When a compressor startup
current/voltage that is at or
below the specified value is
detected.
E22 Circuit malfunction
When a short or open in the
STI internal current/voltage
detection circuit is detected.
E23 E23
Evaporator fan motor
over rotation
abnormality
When an evaporator fan
motor rotates at speed 1150
rpm or above.
Self-Diagnostic
Code
Possible Cause
Alarm
Pattern
Relay Board
LED (Red turns on)
Warning
Signal
Output
Detection Contents
User
Mode
Service
Mode
1 2 3 4 5 6