8.10 Inspection of Refrigeration System
In most cases, the cause for insufficient cooling is a clog in the system, a leakage, or an incorrect
amount of refrigerant. In such cases, inspect the system according to the following procedure.
(1) Clogged refrigeration system
Check the component parts of the refrigeration system, including piping, that could be clogged
with refrigerant. If clogged with refrigerant, only the clogged part is partially frosted. If this occurs,
change the part in question.
(2) Refrigerant leak
Carefully check all connections, and each component for leaks whenever the refrigeration
system is installed or repaired. Use an electronic gas leak tester to inspect the system. (See
page 76 to 86.)
(3) Insufficient refrigerant
When the unit is not producing sufficient cooling, follow the troubleshooting chart on page 58 to
confirm the cause of the problem. Then, charge the system with the refrigerant to the specified
amount as indicated on page 85.