Operation Section
8
2.2 Technical Specifications
ITEM SPECIFICATIONS
Electronic Features Control Wall Mounted Controller (Included)
Set Point
Temperature Range
Max. 95 °F (35 °C)
Min. 55 °F (13 °C)
Electrical Characteristics Voltage Requirement Single-Phase, 208/230 V, 60 Hz
Operating Voltage
Range
Max. 253 V
Min. 198 V
Starting Current 11.5 A
Recommended Fuse Size 20 A
FLA 9.6/8.9 A
MCA 13.5 A
MOP 23 A
LRA 20.6 A
Cooling Capacity and Power Consumption
Air: 80 °F (27 °C), 50 %RH
Water (EWT/LWT): 85 °F/
95 °F (29 °C/35 °C)
Total Cooling Capacity
*1
29400/29400 Btu/h (8640/8640 W)
Sensible Cooling Capacity
*1
20400/20800 Btu/h (6000/6120 W)
Power Consumption
*1
1.93/1.99 kW
Current Consumption
*1
9.6/8.9 A
Power Factor 97/97 %
Air: 75 °F (24 °C), 50 %RH
Water (EWT/LWT): 86 °F/
95 °F (30 °C/35 °C)
Total Cooling Capacity
*1
25200/25200 Btu/h (7380/7380 W)
Sensible Cooling Capacity
*1
21400/22000 Btu/h (6300/6420 W)
Power Consumption
*1
1.95/2.00 kW
Current Consumption
*1
9.6/9.0 A
Power Factor 98/97 %
IEER 17.0
Compressor Type of Compressor Hermetic Swing Inverter
Output Variable
Evaporator Type of Evaporator Plate Fin
Type of Fan Centrifugal Fan
Air Flow High 1000/1060 CFM (1700/1800 m
3
/h)
Low 770/840 CFM (1300/1430 m
3
/h)
Max. External Static Pressure 0.66 IWG (165 Pa)
Motor Output High 180/240 W
Low 84/104 W
Condenser Type of Condenser Water Cooled, Coaxial Coil
Water Flow Rate 7.1 gal/min (27 L/min)
Type of Water Control Refrigerant Discharge Pressure