Repair Section
66
3) Take out the twenty-one (21) screws, and then
remove the top panel.
4) Open the faucet handle to supply water.
5) Insert screwdrivers under both sides of the valve
spring guide of the water regulating valve and lift
upwards to flush. This manual flushing does not
affect valve adjustment.
CAUTION
• Do not move the adjusting bolt.
• Take caution to prevent any corrosion inside
the copper tube if cleanser is used to clean the
water line.
6) Keep flushing the water inside the water line
through the drain until the water is clear.
7) Disconnect tap water from the water inlet and
outlet of the unit.
ILL00242-00
Screws (5)
Screws (6)
Top Panel
Top Panel
Screws (4)
Screws (6)
ILL00436-00
Valve Spring
Guide