MGate 5105-MB-EIP Series User Manual
The provided Diagnose pages under the option of Protocol Status can help identify whether any protocol
communication issues happened. (E.g., invalid response or timeout issue)
NOTE
When the MGate gateway acts as an EtherNet/IP adapter, the OT instance is 100 and TO instance is
110. Your EtherNet/IP scanner (e.g. PLC, SCADA) needs to use these two instances to communicate with
the MGate. For example, provide an Output (i.e., OT) instance of 100 and an Input (i.e., TO) instance
of 110 for a Rockwell PLC, as shown below.