EasyManua.ls Logo

Moxa Technologies MGate 5105-MB-EIP Series - Power Input and Relay Output Pinouts; LED Indicators

Moxa Technologies MGate 5105-MB-EIP Series
81 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MGate 5105-MB-EIP Series User Manual
6
Power Input and Relay Output Pinouts
V2+ V2-
V1+ V1-
Shielded
Ground
DC Power
Input 2
DC Power
Input 2
N.O. Common N.C.
DC Power
Input 1
DC Power
Input 1
LED Indicators
LED
Description
PWR 1,
PWR 2
Power is on
Power is off
Ready
Power is off or a fault condition exists
Green
Steady: Power is on, and the MGate is functioning normally
Blinking: The MGate has been located by MGate Manager’s Location
function
Red
Steady: Power is on, and the MGate is booting up
Blinking slowly: shows an IP conflict, or the DHCP or BOOTP server is not
responding properly
Flashing quickly: microSD card failed
EIP (Scanner)
No I/O data is exchanged
Green
Steady: I/O data is exchanged with all devices
Blinking: I/O data is exchanged with at least one device
(not all configured devices can communicate with a gateway)
EIP (Adapter)
No I/O data is exchanged
Green
Steady: I/O data is exchanged with all devices
Blinking: I/O data is exchanged with at least one device
(not all configured devices can communicate with a gateway)
MB
No communication with Modbus RTU/ASCII device
Modbus RTU/ASCII communication progress
Red
Communication error
When MGate 5105 acts as RTU/ASCII Client/Master:
1. Server/Slave device returned an error (exception)
2. Received frame error (parity error, checksum error)
3. Timeout (server/slave device no response)
When MGate 5105 acts as RTU/ASCII Server/Slave:
1. Received invalid function code
2. Client/Master accessed invalid register address or coil addresses
3. Received frame error (parity error, checksum error)

Table of Contents