MGate 5105-MB-EIP Series User Manual
Power Input and Relay Output Pinouts
V2+ V2-
V1+ V1-
N.O. Common N.C.
LED Indicators
PWR 2
Ready
Power is off or a fault condition exists
Green
Steady: Power is on, and the MGate is functioning normally
Blinking: The MGate has been located by MGate Manager’s Location
function
Red
Steady: Power is on, and the MGate is booting up
Blinking slowly: shows an IP conflict, or the DHCP or BOOTP server is not
responding properly
Flashing quickly: microSD card failed
EIP (Scanner)
Green
Steady: I/O data is exchanged with all devices
Blinking: I/O data is exchanged with at least one device
(not all configured devices can communicate with a gateway)
EIP (Adapter)
Green
Steady: I/O data is exchanged with all devices
Blinking: I/O data is exchanged with at least one device
(not all configured devices can communicate with a gateway)
MB
No communication with Modbus RTU/ASCII device
Modbus RTU/ASCII communication progress
Red
When MGate 5105 acts as RTU/ASCII Client/Master:
1. Server/Slave device returned an error (exception)
2. Received frame error (parity error, checksum error)
3. Timeout (server/slave device no response)
When MGate 5105 acts as RTU/ASCII Server/Slave:
1. Received invalid function code
2. Client/Master accessed invalid register address or coil addresses