MGate 5105-MB-EIP Series User Manual
Master Mode Settings
The MGate 5105-MB-EIP supports Modbus TCP Client (Master) mode, which means the MGate will work as a
client and send the Modbus command request to the server/slave device actively. You will need to configure
each Modbus command manually. On this page, users can see all the commands listed in the table.
Initial Delay 0 to 65535 ms
Some Modbus servers/slaves may take more time to boot
up than other devices. In some environments, this may
cause the entire system to suffer
during the initial boot-up. You can force the MGate to wait
after booting up before sending the first request with the
Initial Delay setting.
Response Timeout 10 to 12000 ms
This is used to configure how long the MGate will wait for a
response from a Modbus server/slave.
Max. retry 0 to 99
This is used to configure how many times the MGate will
try to communicate with the Modbus server/slave.