10 Maintenance
Maschinenfabrik Reinhausen GmbH 2023 754001150/12 EN MSENSE
®
DGA 2/3
4. Select the gases for which you want a field calibration. Enter the labora-
tory results as the reference corresponding to the respective gas.
Figure52: Field calibration step1
5. Enter the date of the oil sample from the laboratory results.
Figure53: Entering the date