OBSERVER-i HART
25
10.23 COMMAND #170: SET CURRENT RANGE
This command sets the 4-20mA analog output range.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
0 Range 3.5 mA 20 mA, 1 -- Range 1.25 20 mA
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
0 Range 3.5 mA 20 mA, 1 -- Range 1.25 20 mA
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1 - 2
Undefined
3
Error
Passed Parameter Too Large
4
Undefined
5
Error
Too Few Data Bytes Received
6 - 127
Undefined
10.24 COMMAND #171: SET DETECTION MODE
This command sets the Detection Mode.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
0 Classic Mode, 1 Enhance Mode
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
0 Classic Mode, 1 Enhance Mode
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1 - 2
Undefined
3
Error
Passed Parameter Too Large

Table of Contents