Fault code No. Full designation Meaning Action
Related
parameter
No.
465 SD P-AUX 2
SD alarm configuration; Ana-
log input signal for Aux 2
pressure faulty; Short circuit
or wire break
Check pressure
transmitter and ca-
bling, replace as
necessary.Error
cleared after re-
starting the engine.
1.8004.58
8
466 SD T-AUX 2
SD alarm configuration; Ana-
log input signal for Aux 2
temperature faulty; Short cir-
cuit or wire break
Check temperature
sensor and cabling,
replace as necessa-
ry. Error cleared af-
ter restarting the
engine.
1.8004.58
6
467 L2 T-Aux 1
Alarm configuration limit val-
ue 2; Preliminary warning:
Temperature signal of Aux 1
has exceeded / not attained
limit value 2, depending on
configuration.
Determine cause of
limit value violation
and rectify fault.
2.0130.92
2
468 SD T-AUX 1
SD alarm configuration; Ana-
log input for Aux 1 tempera-
ture faulty. Replace ECU. 1.8004579
469 SD AUX 1
SD alarm configuration; Ana-
log input signal for Aux 1
faulty; Short circuit or wire
break
Check signal trans-
mitter and cabling,
replace as necessa-
ry.Error cleared af-
ter restarting the
engine.
1.8004.59
0
470 SD T-ECU
SD alarm configuration; Tem-
perature sensor for ECU faul-
ty; Short circuit or wire break
Check sensor and
cabling, replace as
necessary.Error
cleared after re-
starting the engine.
1.8004.58
7
471
SD HP Fuel Control
Block
SD alarm configuration; Con-
trol of HP fuel control block
faulty; Short circuit or wire
break
Check sensor and
cabling, replace as
necessary.Error
cleared after re-
starting the engine.
1.8004.59
2
472 AL Stop SD
Alarm configuration; Engine
shutdown, since all shut-
down channels have “sensor
faulty”.
1. Check cabling.
2. Contact Service.
2.8006.59
3
473 AL Cabling PWM_CM2
Alarm configuration; Cable
break or short circuit on
channel PWM_CM2.
1. Check cabling.
2. Contact Service.
1.8004.59
3
474 AL Cabling FO
Alarm configuration; Cable
break or short circuit on
channel FO.
1. Check cabling.
2. Contact Service.
2.8006.65
5
475
AL CR Engine Shutdown
Trigger
Alarm configuration; activat-
ed when crash recorder trig-
gered by an engine shutdown
Determine and rec-
tify cause of trig-
gering / engine
shutdown.
1.8010.00
9
76 | Troubleshooting | M015695/03E 2013-03