7.4 Technicaldata
MCD100E M CD120E M CD140E MCD155E
Processair
Figuresquotedare rated,based ona faninlettemperatureof
20°Cand an airdensityof1,2kg/m
3
.
Ratedairflow(m
3
/s) 2,78 3,33 3,89 4,25
Ratedairflow(m
3
/h) 10000 12000 14000 15300
Minimum availablestati
cpressure(Pa)
300 300 300 300
Fanmotorpower(kW) 11 11 11 11
Reactivation air
Ratedairflow(m
3
/
s)
0,850 1,100 1,250 0,850
Ratedairflow(m
3
/h)
3060 3960 4500 3060
Minimumavail
ablestaticpressure(Pa)
300 300 300 300
Fanmotorpow
er(kW)
2,2 4,0 4,0 2,2
Reactivat
ion heater
Temperat
ureincreaseacrossheater(°C)
100 100 100 100
Reacti
vationheaterpower(kW)
102 132 150 102
React
ivationheaterpower, ERP(kW)
90 120 132 90
Tot
alrequiredpow er (50Hz)
Wi
thprocessandreactivationfan(kW)
11
5,9
14
7,7
16
5,7
11
5,9
W
ithERP(kW)
1
03,9
1
35,7
1
47,7
1
03,9
Withoutprocessfan(kW) 104,9 136,7 154,7 104,9
Ratedc urrent w ith
processand reactivationfan,Standard /EEP
380V,3~50 Hz (A) 182 232 259 182
400V,3~50 Hz (A) 173 220 246 173
415V,3~50 Hz (A) 167 212 237 167
Ratedc urrent w ith
processand rea ctivationfan,ERP
380V,3~50 Hz (A) 164 213 234 165
400V,3~50 Hz (A) 157 204 224 158
415V,3~50 Hz (A) 153 198 217 153
44