CAUTIO N!
Nevermove thedehumidifierwhenthe processfanandfilterboxhavebeeninstalled. Failure toobserve this will
causedamage tothe dehumidifier.
3.5 Storingthedehum idifier
The following is impor tant if t he dehumidifi er is to be stored prior to installation:
■
Place the dehumidifier in an upright position on a horizontal surface.
■
Protect the dehumidifier from physical damage.
■
Store the dehumidifier under cover and protect it from dust, frost, rain and agg r essive contaminants.
See section 7.4, Technical data for cor rect storage temperature.
3.6 Siterequirements
NOTE!
Itisimportantthattheintendedinstallationsitemeetstherequirementsinordertoachievethebest
possible performanceandtrouble-free operation.
NOTE!
Itis importantforbothmaintenanceandservice purposesthatthe minimum servicespacerequirements
arecompliedwith.
Thedehumidifier is only intended for indoor installation. Avoid installing the dehumidifier in a damp
environment where there is a risk of water entering the unit, or in a very dusty environment. Refer to
Munters for advice if in doubt.
NOTE!
Ifthereisaneedforreduction ofvibrations fromthedehumidifier, contactMunters forinstructions. Refer
tostandardEN1299+A1:2008.
See section 7.3, Dimensions a nd service sp ace for unit and service dimensions.
3.7 Splitunitinstallation
WARNING!
To prevent personal injuryordamage tothe dehumidifier,alwaysuseapprovedliftingequipment.
WARNING!
Checkthatthelifting equipmentiscapableof supportingthetopbox beforelifting.
Seesection 7.4,Technical dataforweightdata.
CAUTIO N!
Aliftingframewithfourslingsmustbeusedwhenliftingthetopbox. Theliftinganglemustnotexceed15°,
seeFigure 3.9.