FlexPAK 800/1000EN
12
3.1.8 Close Upper Slide Valve V12
The message appears when the TVFD Upper Solenoid Valve is expected to close. The
mer is set with TVFDC-Al, see Secon ‘4.2.26 TVFD-Al-Tmr’. If the mer elapses, the
‘TVFD Alarm! Upper Slide Not Closed is acvated. This message is only shown when TVFD
advanced is acvated.
ESC OK
Close Upper
Slide Valve
Remaing me
08:00s
Remaining Time: The remaining me for the valve to close before the
alarm is acvated.
3.1.9 Emptying bin TVFD Advanced
The message appears when the TVFD Lower Solenoid Valve is expected to open. The mer
is set with TVFDC-Al, see Secon ‘4.2.26 TVFD-Al-Tmr’. If the mer elapses, the ‘TVFD
Alarm! Lower Slide Not Open is acvated. This message is shown when TVFD advanced is
acvated. TVFD-Al is only acvated when using TVFD advanced.
ESC OK
EMPTYING BIN
Open Lower
Slide Valve
Remaing Time
02:00s
Remaining Time: The remaining me for the valve to open before the
alarm is acvated.
3.1.10 Close Lower Slide Valve V11
The message appears when the TVFD Lower Solenoid Valve is expected to close. The
mer is set with TVFDC-Al, see Secon ‘4.2.26 TVFD-Al-Tmr’. If the mer elapses, the
‘TVFD Alarm! Lower Slide Not Closed is acvated. This message is only shown when TVFD
advanced is acvated.
ESC OK
Close Lower
Slide Valve
Remaing time
05:00s
Remaining Time: The remaining me for the valve to close before the
alarm is acvated.
3.1.11 Flushing duct
The unit is ushing the duct system. This message is shown when FlushCy1 and FlushCy2
acvate the ush valve. This message is also shown when FlushTemp is acvated, see
Secons ‘4.2.30 FlushCy1’, ‘4.2.22 FlushCy2’ and ‘4.2.24 FlushTmp’.
ESC OK
Flushing
Ducts
Cycl 1 03:00 s
Cycl 2 05:00 s
Cycl1: The me remaining for the ush cycle with the ush valve 1
(SFV1).
Cycl2: The me remaining for the ush cycle with the ush valve 2
(SFV2).