FlexPAK 800/1000EN
24
4.2.5 CoolTmr
CoolTmr cools the unit by open Cleaning Valve V1 “SCV” to cool the vacuum pump. The
CoolTmr mer funcon is started by CoolTmp.
When the fan’s outgoing air temperature is over the CoolTmp threshold, “On=97”, CoolTmr
is acvated and opens Cleaning Valve V1 (SCV).It keeps the valve open for (TH=X seconds),
and then closes the valve independent of whether the fan’s outgoing air temperature is
over the CoolTmp threshold “On=97”, or below the threshold level CoolTmp O “O=96”.
Set the TH parameter to maximum allowed cooling me in X seconds.
The default sengs for CoolTmr; CoolTmr is not acvated:
ESC OK
CoolTmr 1/1
TH = 00:00s
TL = 00:00s
Ta = 00:00
TH= 0 seconds: the Cleaning Valve V1in is opened for 0 seconds. TH= 0
is the default seng. To acvate CoolTM, set CoolTM TH > 0 seconds
(e.g. TH= 5).
TL= 0 seconds: (The default seng, do not change).
TA= Ta=00:00: The elapsed me since the Cooling cycle was acvated.
To acvate CoolTmr, use the following sengs:
ESC OK
CoolTmr 1/1
TH = 05:00s
TL = 00:00s
Ta = 00:00
TH= 5 seconds: the Cleaning Valve V1in is opened for 5 seconds. TH= 0
is the default seng. To acvate CoolTM, set CoolTM TH > 0 seconds
(e.g TH= 5).
TL= 0 seconds: (The default seng, do not change).
TA= Ta=00:00: The elapsed me since the Cooling cycle was acvated.
4.2.6 FltClean
Menu for seng me between automac lter cleanings. If TH = 0, no lter cleaning is
performed. TH may not be set to 0 if PSIFC is set to ‘On’.
ESC OK
FltClean 1/1
TH = 01:00s
TL = 60:00m
Ta = 00:00m
TH=01:00s: Do not change the default seng of 1 second.
TL=60:00m: Time between automac lter cleanings. The default
seng is 60 minutes.
Ta=00:00: The elapsed me since the last automac cleaning was
acvated.
4.2.7 DIR_Time
Menu for seng the DIR mer. The DIR mer is the amount of me before the unit goes
from Running mode into Idling mode when the pilot signal disappears.
ESC OK
DIR_Time 1/1
T = 10:00s
Ta = 00:00s
T=10:00 seconds: Time before DIR_Time is acvated. The default seng
is 10 seconds The minimum seng is 5 seconds.
Ta=00:00 seconds: The elapsed me since the pilot signal disappeared.
4.2.8 Weekly Timer
See secon ‘4.2.2 Set the weekly mer.
ESC OK
WeekTmr 1/2
D1 = - - - - - - -
On1 = -- : --
Off1 = -- : --
D2 = - - - - - - -
On2 = -- : --

Table of Contents

Other manuals for Nederman FlexPAK 800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nederman FlexPAK 800 and is the answer not in the manual?

Nederman FlexPAK 800 Specifications

General IconGeneral
BrandNederman
ModelFlexPAK 800
CategoryDust Collector
LanguageEnglish

Related product manuals