FlexPAK 800/1000EN
26
4.2.13 BLI-Wr
Menu for seng the delay me for the Bin Level Indicator warning message. When the
BLI signal disappears, the BLI-Wr mer is acvated. When the mer elapses, the message
‘Warning! Dustbin Full’ is acvated, see Secon ‘3.2.3 Dustbin Full’.
ESC OK
BLI-Wr 1/1
T = 12:00m
Ta = 00:00m
T=12:00m: Time before message “Warning! Dustbin Full’ is acvated.
Default is 12 minutes.
Ta=00:00: Elapsed me since the BLI-sensor was acvated.
4.2.14 AEBTme
Menu for Automac Emptying of the collector Bin, interval Timer sengs. This funcon
is only available when BinAuto is set to ‘On’, see Secon ‘4.2.19 BinAuto’. When AEBTme
elapses, it acvates the dust bin emptying sequence with either the AEB - Flap Valve,
simple TVFD, Advance TVFD or Preseparator.
ESC OK
AEBTmr 1/1
TH = 01:00s
TL = 60:00m
Ta = 00:00m
TH=01:00s: Do not change the default seng of 1 second.
TL=60:00m: The amount of me between emptying cycles. The default
seng is 60 minutes.
Ta=00:00: The elapsed me since the last AEB was acvated.
4.2.15 BinOpnTm
Menu for AEB-Flap Valve, simple TVFD and Preseparator opening cycle sengs. The values
for ‘TL’ and ‘TH’ depend on which funcon is being used. See Secon ‘5 Automac bin
emptying funcon’.
ESC OK
BinOpnTm 1/1
TH = 05:00s
TL = 03:00s
Ta = 00:00s
TH= See Secon ‘5 Automac bin emptying funcon’.
TL= See Secon ‘5 Automac bin emptying funcon’.
4.2.16 CFDPS-Al
Menu for seng the delay me for the Control Filter DP Sensor Alarm (CFDPS-Al). When
the Control Filter DP Sensor signal disappears, the CFDPS-Al mer is acvated. When this
mer has elapsed, the unit goes into O mode and an alarm is displayed in the PLC. See
Secon ‘3.3.8 Alarm! Control Filter Clogged’.
ESC OK
CFDPS-Al 1/1
T = 5:00s
Ta = 00:00s
T=05:00s: Time before CFDPS-Al is acvated. The default seng is 5
seconds.
Ta=00:00: The elapsed me since the CF-DPS signal disappeared.
4.2.17 TVFDAdv
Menu for acvang the advanced TVFD where an upper and lower posion sensor are used
to detect TVFD valve posion.
ESC OK
TVFDAdv 1/1
Switch = Off
Switch=O is the default seng; advanced TVFD is deacvated. Simple
TVFD, AEB or Preseparator is acvated.
To acvate advanced TVFD, set Switch=On.

Table of Contents

Other manuals for Nederman FlexPAK 800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nederman FlexPAK 800 and is the answer not in the manual?

Nederman FlexPAK 800 Specifications

General IconGeneral
BrandNederman
ModelFlexPAK 800
CategoryDust Collector
LanguageEnglish

Related product manuals