FlexPAK 800/1000
33
EN
4.2.38 BLI-Alarm
Menu for seng the delay me for the Bin Level Indicator Alarm message. When the BLI
signal disappears, the BLI-Alarm mer is acvated. When the mer elapses, the Alarm
message “Alarm! Dustbin Full” appears and the vacuum unit is stopped.
ESC OK
BLI-Alarm 1/1
T = 30:00m
Ta = 00:00m
T=30:00m: Time before Alarm! Dustbin Full message is acvated. The
default is 30 minutes.
Ta=00:00: Elapsed me since the BLI-sensor was acvated.
4.2.39 MFDPS-Al
Menu for seng the Main Filter Dierenal Pressure Sensor Alarm (MFDPS-Al) delay mer.
When the Main Filter Dierenal Pressure Sensor signal disappears, MFDPS-Al is acvated.
When the delay mer has expired, the “Alarm! Main Filter Clogged” message is acvated.
See Secon ‘3.3.15 Alarm! Main Filter Clogged’.
When the mer has expired, the unit stops.
ESC OK
MFDPS-Al 1/1
T = 20:00m
Ta = 00:00m
T=30:00m Time before MFDPS-Al is acvated. The default is 30
minutes.
Ta=00:00 Elapsed me since the MFDPS signal disappeared.
4.2.40 DPFClean
Menu for acvaon and deacvaon of DPFClean. When acvated, this funcon causes the
Main Filter Dierenal Pressure to acvate cleaning of the main lter.
When the seng for the maximum dierenal pressure has been exceeded, the Main Filter
Dierenal Pressure Sensor signal disappears and it cause MFDPS-FC to be acvated, which
delays the start of the cleaning cycle. The delay is designed to lter away a temporarily high
dierenal pressure over the main lter. See Secon ‘4.2.11 MFDPS-FC’.
ESC OK
DPFClean 1/1
Switch = Off
Switch=O is the default seng; DPFClean is deacvated.
To acvate DPFClean, set Switch=On.
4.2.41 EmtyIdli
Menu for acvang automac dust bin emptying when the unit goes into Idling Mode.
ESC OK
EmtyIdli 1/1
Switch = Off
Switch=O is the default seng. EmtyIdli is deacvated.
To acvate EmtyIdli, set Switch=On.