FlexPAK 800/1000
31
EN
4.2.31 VacLoTm
Delay Timer for “Warning! Low Vacuum”, see secon ‘3.2.5 Warning Low Vacuum’ and
secon ‘4.2.28 Vac_Low’.
This mer delays showing the message “Warning! Low Vacuum “ when the vacuum is too
low in the system. The mer serves as a lter to remove short-term vacuum variaons in
the system. When the mer expires, the message “Warning! Low Vacuum “ is displayed.
ESC OK
VacLoTm 1/1
T = 01:00m
Ta = 00:00m
T = 01: 00m default seng 1 minute delay
Ta = 00: 00m shows the lukewarm delay me
4.2.32 PSIFC
Menu for acvang Pilot Signal Interlock Filter Cleaning (PSIFC). Filter cleaning does not
take place unl the pilot signal has disappeared and DIR_Time has expired.
If AEB-TVFD is set to ‘On’ , in other words, AEB-Flap Valve opening is chosen, the bin
emptying sequence is also interlocked when there is a pilot signal to the unit.
ESC OK
PSIFC 1/1
Switch = Off
4.2.33 PresepTm
Menu for AEB-Flap Valve, simple TVFD and Preseparator opening cycle sengs. The values
for ‘TL’ and ‘TH’ depend on which funcon is being used. See Secon ‘5 Automac bin
emptying funcon’.
ESC OK
PresepTm 1/1
TH = 05:00s
TL = 03:00s
Ta = 00:00s
TH= See Secon ‘5 Automac bin emptying funcon’.
TL= See Secon ‘5 Automac bin emptying funcon’.
4.2.34 FlushTmr
Menu for automac ushing of the duct system with the interval mer. FlushTmr acvates
FlushCy1 and FlushCy2. FlushTmr is deacvated if PSCFlush is acvated ‘Switch=On’, see
Secon ‘4.2.18 PSCFlush’.
ESC OK
FlushTmr 1/1
T = 30:00m
Ta = 00:00m