3.3.4 Low Pressure or Duct Isolaon Released
The Compressed Air Switch (CAS) indicates that the compressed air pressure is too low.
Or, there is a duct isolaon valve connected to the system that has released and isolated
FlexPAK from the duct system. Check the isolaon valve release sensor, released isolaon
vale = open electrical circuit to input on PLC.
Press the green OK buon
OK
to reset the alarm.
ESC OK
Low Pressure
CAS<3Bar Or
Duct Isolation
Valve Released
Th 11:23
Reset OK ==>
3.3.5 Alarm! Hi Vacuum
The maximum vacuum level has been acvated, and the delay me for the vacuum alarm
has elapsed. Press ‘OK’ to reset the alarm.
ESC OK
Alarm!
Hi Vacuum
Level > -36 kPA
Th 12:23
Unit is Stopped
Reset OK==>
3.3.6 Exhaust Air Temp High
The temperature of the air exing the pump has exceeded the maximum allowable limit of
135ºC (275ºF). When the ‘Current Value’ has become lower than 90°C (194ºF), press ‘OK’
to reset the alarm. Check for the cooling air valve or PT100 sensor values.
ESC OK
Max Temp Exhaust
Air Exceeded
Unit is Stopped
Limit 135 °C
Current 130 °C
Reset OK
3.3.7 Bag Replacement Switch Time Out
The maximum amount of me for the bag replacement being ‘On’ has been exceeded. To
restart the unit, the alarm needs to be reset by turning the bag replacement switch (SC2)
to ‘O‘ and pressing the green OK buon
OK
to reset the alarm.. See also Secon ‘4.2.27
BRSTmr’.
ESC OK
Bag Replacment
Switch Time Out
Th11:23
Unit is Stopped
Reset OK ==>