4.2.28 Vac_Low
Menu for seng the warning level for Low vacuum in the system.
When the vacuum level is above the set limit value, a warning message appears on the
display. The warning message is delayed to lter messages that would otherwise be
acvated by temporary pressure changes in the system. This is to avoid unnecessary and
annoying warning messages.
In other words, if the limit is set to -15kpa and the pressure in the system is -14kPa, the
alarm will be acvated when the VacLoTm delay mer has expired.
Warning Message Acvated = “Warning Low Vacuum”
Limit seng: Vaccum 15kPa = Pressure -15kPa
Default seng: On = -15 kPa
Default seng: O = -15 kPa
On and O must have the same limit value.
ESC OK
Vac_Low 1/1
On = -15
Off = -15
4.2.29 AEB-TVFD
Menu for choosing between the AEB-Flap Valve or simple TVFD for automac bin emptying:
• AEB-TVFD = O: Simple TVFD is selected.
• AEB-TVFD = On: AEB-Flap Valve is selected.
When the AEB-Flap Valve is acvated, the TVFD solenoid upper valve is closed and the
unit’s motor is slowed down when the collector bin is being emped. The Solenoid Upper
Valve can be used to control a Duct isolaon valve. When Simple TVFD is acvated,
the motor is not slowed down when the collector Bin is being emped. See Secon ‘5
Automac bin emptying funcon’.
ESC OK
AEB-TVFD 1/1
Switch = On
Switch=On is the default seng. AEB-TVFD is acvated.
To deacvate AEB-TVFD set Switch=O.
4.2.30 FlushCy1
Menu for seng the amount of me for automac ushing of the duct system by ushing
valve 1 (SFV1). If PSCFlush is deacvated, FlushCy1 is acvated by FlushTmr. If PSCFlush is
acvated and there is no pilot signal. ‘T’ is how long the ushing valve is open.
ESC OK
FlushCy1 1/1
T = 10:00s
Ta = 00:00s
T=10:00s: Time ush valve 1 (SFV1) is open. The default seng is 10
seconds.
Ta=00:00: The elapsed me since the ushing cycle started.