V. System Operations and Controls
D. Automatic System Operation (continued)
14. Allow the machine to operate. During operation, various indicator lamps will illuminate
and turn off. Input, nitrogen venting, and pump out of AGENT will cycle until all of the
Agent has been extracted from the source container. PROCESSING OF AGENT FROM
THE SOURCE CONTAINER IS NOT COMPLETE UNTIL THE AGENT PROCESSING
LAMP OF THE MACHINE IS NO LONGER CONTINUOUSLY ILLUMINATED. The
processing lamp may flash on and off to indicate an error condition. When the
processing lamp flashes: the source container may not be empty. Refer to section-
VIII.A. of this manual for a description of the error codes.
15. When the processing lamp of the front panel goes out and the pressure gauge of the
front panel indicates a vacuum condition:
Close the Manual Inlet Valve of the machine.
Close the Valve on the Source Container.
Disconnect the source container from the machine.
WARNING: Always verify that the source container is in a vacuum using the inlet
pressure gauge located on the front panel of the machine before
disconnecting the source container from the machine. Some system fire
extinguisher tanks with automatic discharge heads may automatically
close again during processing before the tank is empty. Attempt to again
activate the discharge mechanism of the tank or use any other appropriate
method to verify that the tank really is empty before disconnecting the
tank from the machine.
The machine is immediately ready to process another source container. Install
the next AGENT source, containing the Agent to be processed, to the Inlet port
of the machine per section-IV.G: Source Container Installation.
Refer to section-V.E: Disconnecting the Source Container When it is not Empty if
it becomes necessary to disconnect the agent source container from the inlet of
the machine before the machine finishes processing in the automatic mode.
Refer to section-V.F: Receiving Container Replacement to replace a full receiving
container with a new empty container when continuing processing.
Refer to section-V.G: System Shutdown when discontinuing processing.